Attackers are exploiting Node-RED CVE-2026-58115 (CVSS 10.0): if the editor has no login set, one POST gives them a shell
Node-RED's editor has no login by default. If it is reachable, anyone can deploy a flow, and a flow is enough to get a shell — that is CVE-2026-58115. It works because two built-in nodes do the whole job. The inject node fires as soon as the flow is deployed. The exec node runs a shell command. Connect the two and the command runs with maximum privileges, with no credentials needed anywhere in the chain. Siemens disclosed this back in August and scored it 10.0. The CVE is written against its SIMATIC IoT2050 Advanced gateways: Industrial OS with Node-RED installed, any version before V4.3.4.1. The fix is V4.3.4.1 or later. Siemens also says Node-RED can be removed from the device instead
…